Western Reserve Controls WRC-CANR-DF-DN and –SM User’s Manual
PUB 14.2 Revision 4.03
9
Table 4-5 Baud Rate Settings for Switches
Baud rate
Local Position 1
Position 2
Position 3
Position 4
Meaning
Remote Position 5
Position 6
Position 7
Position 8
125K CLOSED CLOSED CLOSED CLOSED Fixed
250K CLOSED CLOSED CLOSED
OPEN
Fixed
500K CLOSED CLOSED
OPEN
CLOSED Fixed
Autobaud CLOSED CLOSED
OPEN OPEN
Autobaud for DeviceNet
Bauds (125k,250k,500k)
9.6K CLOSED
OPEN
CLOSED CLOSED Fixed
10K CLOSED
OPEN
CLOSED
OPEN
Fixed
20K CLOSED
OPEN OPEN
CLOSED Fixed
40K CLOSED
OPEN OPEN OPEN
Fixed
50K
OPEN
CLOSED CLOSED CLOSED Fixed
100K
OPEN
CLOSED CLOSED
OPEN
Fixed
800K
OPEN
CLOSED
OPEN
CLOSED Fixed
1M
OPEN
CLOSED
OPEN OPEN
Fixed
Remote
OPEN OPEN OPEN OPEN
Takes baud rate from the
opposite end device. If
both sides are remote,
Autobaud from either side.
Autobaud ALL OTHER SWITCH POSITIONS Autobaud
4.4. Power Requirements
The WRC-CANR-DF CAN-Bus Extender subsystems are powered from the 11-25 Vdc provided
by the DeviceNet network. The WRC-CANR consumes 60 mA of current at 25 Vdc, or 1.5 Watts, typical.
See Section 3.
4.5. CAN Network Cabling and Configuration
This section provides general guidelines for connecting DeviceNet and SDS systems. You can
find detailed specifications in the referenced ODVA DeviceNet and Honeywell SDS specifications.
4.5.1. Cable Lengths
The following provide cable length limits for DeviceNet and SDS systems. These numbers apply
independently to each physical section of the CAN (copper) network.