Western Reserve Controls WRC-CANR-DF-DN and –SM User’s Manual
PUB 14.2 Revision 4.03
21
8. Summary of Changes to Series IV from Rev 2 and
Series III
To facilitate implementation of the new Series III CANR products for customers that are currently
users of the CANR Revision 2.xx products, this section summarizes the product changes from Rev 2 to
Series 3.
8.1. DIP Switch Baud Rate Settings
Several new options exist for setting the baud rate on the CANR Series IV.
Like the Series III, the Series IV has an 8-position DIP switch block. All 8 switches are
defined and used.
The Series IV unit is compatible with all CANopen baud rates. These baud rates are fixed
by setting the 8 position dip switch to the appropriate configuration.
See Section 4.3 for details.
8.2. Terminating Resistors
The Series IV has an on-board terminating resistor on the CAN connection that can be selectively
included or excluded from the network circuit. With jumpers W1, the CANR puts a 121-ohm resistor
across the CAN_H and CAN_L lines on sub-network side A. See Section 4.5.2 and Table 4-8 for the
location of this jumper.
8.3. Operation and Functionality
The Rev 2 version CANR required one Type 1 and one Type 2 unit per connection. The Series III
and IV products now make no differentiation there is only one design. Therefore, you do not need to be
concerned with “matching pairs”.
Important
:
The
Series III and IV products are not backwards compatible with the previous
versions
.
You cannot implement a network which consists of a Revision 2 product on one end of the fiber
and a Series III or IV on the other end. The same is true with networks with a Series III on one end and a
Series IV on the other:
this will not perform
.
8.4. 2.2km Multimode Fiber Link and Diagnostics (WRC-CANR-
DF-DN)
The WRC-CANDF-DN Series III and IV have the following fiber serial link improvements:
Extends your applications for up to 2.2km at any CAN baud rate.
o This significantly increases opportunities for mining, tank farm, remote out-
buildings, and other similar applications.